Diagnostic codes

Note
This documentation refers to the monitored pressure-sensitive protective equipment as PSE for short.

The hexadecimal diagnostic codes listed here are output as WORD data type at the DiagCode output of the function block.

Code (hex)DescriptionOptions for remedy
0000 The function block is not activated. The Activate input is FALSE.

Depending on the connection of Activate, the inactive function block can also indicate an error in the connected periphery.
Activate the function block by switching Activate to TRUE.

Correct the error in the periphery according to the device description.
8000 The PSE has not triggered (S_PSE_In = SAFETRUE). No measures required.
8001The function block is activated. This state of the function block is completed after one cycle of the Safety PLC.No measures required.
8802The start-up inhibit is specified with S_StartReset = SAFEFALSE.

  • PSE has triggered (S_PSE_In = SAFEFALSE)
  • or the wiring is damaged or disconnected
  • or the safety-related input device, to which the PSE is connected, is switched off or inoperable.
  • Remove the PSE safety-related request.
  • In case of PSE that has not triggered, verify the wiring and the safety-related input device to which the PSE is connected.
8402The PSE is no longer triggered (S_PSE_In = SAFETRUE).
The start-up inhibit of the function block is active.
Perform a reset on the function block.
8804PSE has triggered (S_PSE_In = SAFEFALSE).

  • PSE has triggered (S_PSE_In = SAFEFALSE)
  • or the wiring is damaged or disconnected
  • or the safety-related input device, to which the PSE is connected, is switched off or inoperable.
  • Remove the request for the safety-related function of the PSE and then perform a reset if S_AutoReset = SAFEFALSE.
  • In case of PSE that has not triggered, verify the wiring and the safety-related input device to which the PSE is connected.
8404The PSE is no longer triggered. The restart inhibit of the function block is active (S_AutoReset = SAFEFALSE).Perform a reset on the function block.
C001Once the request for the safety-related function of the PSE has been removed, a permanent TRUE is detected at Reset.
  • Switch Reset = FALSE.
  • Verify the reset control device and its wiring.
C011Once the request for the safety-related function of the PSE has been removed, a permanent TRUE is detected at Reset.
  • Switch Reset = FALSE.
  • Verify the reset control device and its wiring.