MaxMutingTime input
Specification of the maximum permissible time for the entire muting operation. If the muting operation is not completed within this time, the S_AOPD_Out output is switched to the defined safe state SAFEFALSE and the function block signals an error (Error switches to TRUE).
Data type: TIME
Initial value: #0ms
Connection: Connect this input to a time literal, i.e., to a constant of the data type TIME.
This timer starts when at least one of the two muting sensors provides a SAFETRUE signal (i.e., there is an object inside the detection area of the sensor).
The muting operation is complete when at least one of the muting sensors provides SAFEFALSE again.
| Further Info
Also refer to the example muting operation procedure shown in the functional description for this function block. |
|
WARNING
|
Non-conformance to safety function requirements
|
Minimum value: 0 s
Maximum value: 600 s