Profinet Warning (PNIO0112): The device "..." cannot be updated cyclically faster than "...".
This warning is reported when the update time of the cyclic exchange of IO data between Profinet controller and Profinet device is lower than the minimum value given in the warming. The update time is a product of the controller's send clock, the Profinet timebase and the reduction ratio. If the update time is lower than the minimum value, the Profinet device may reject the connection request.
Double-clicking the warning jumps to the device parameter ('Update time' for inputs or outputs) that causes the warning. For the selected parameter, enter a value in ms that is higher than the minimum time given in the message.