Diagnostic codes
| Note This documentation refers to the monitored pressure-sensitive protective equipment as PSE for short. | 
The hexadecimal diagnostic codes listed here are output as WORD data type at the DiagCode output of the function block.
| Code (hex) | Description | Options for remedy | 
|---|---|---|
| 0000 | The function block is not activated. The Activate input is FALSE. Depending on the connection of Activate, the inactive function block can also indicate an error in the connected periphery. | Activate the function block by switching Activate to TRUE.Correct the error in the periphery according to the device description. | 
| 8000 | The PSE has not triggered (S_PSE_In = SAFETRUE). | No measures required. | 
| 8001 | The function block is activated. This state of the function block is completed after one cycle of the Safety PLC. | No measures required. | 
| 8802 | The start-up inhibit is specified with S_StartReset = SAFEFALSE. 
 | 
 | 
| 8402 | The PSE is no longer triggered (S_PSE_In = SAFETRUE). The start-up inhibit of the function block is active. | Perform a reset on the function block. | 
| 8804 | PSE has triggered (S_PSE_In = SAFEFALSE). 
 | 
 | 
| 8404 | The PSE is no longer triggered. The restart inhibit of the function block is active (S_AutoReset = SAFEFALSE). | Perform a reset on the function block. | 
| C001 | Once the request for the safety-related function of the PSE has been removed, a permanent TRUE is detected at Reset. | 
 | 
| C011 | Once the request for the safety-related function of the PSE has been removed, a permanent TRUE is detected at Reset. | 
 |