S_SafeControl input
This state-controlled input evaluates the status of an upstream safety-related function (requested or not requested).
Data type: SAFEBOOL
Initial value: SAFEFALSE
Connection: Connect this input directly or via other safety-related functions to the enable signal of an upstream safety-related function block, which evaluates a piece of safety equipment connected to the Safety PLC and signals the status (e.g., SF_EmergencyStop for evaluating an emergency-stop control device). Constant SAFETRUE or SAFEFALSE values are not permitted.
If the function block is activated (Activate = TRUE), the possible values at this input lead to the following function block behavior:
| Value | Description | 
|---|---|
| SAFETRUE | The upstream safety-related function has not triggered (normal operation).Refer to the warning below this table. | 
| SAFEFALSE | The upstream safety-related function has triggered. The S_OutControl output is switched to SAFEFALSE. | 
If no start-up inhibit is specified for the function block and no additional operation stop of the standard controller is specified with StaticControl = TRUE, the SAFETRUE status at the S_SafeControl input can cause the S_OutControl output to switch to SAFETRUE immediately.
|  WARNING | 
| Unintended start-up If no start-up inhibit and no additional operation stop of the standard controller (StaticControl = TRUE) is specified: 
 | 
| Note To control the restart behavior of the function block following a signal change from SAFEFALSE to SAFETRUE at the S_SafeControl input (once the request for the safety-related function has been removed), you can specify a restart inhibit at S_AutoReset. |