Implementation of safety requirements from applicable standards
The safety-related function block has been developed according to the safety requirements (from applicable standards) listed in this section. All other requirements from these standards must be observed when implementing the safety-related function.
This section describes either how the function block meets the requirements of the standards or what measures need to be taken to meet the requirements of the standards.
Standards | Context/Requirement | Implementation | |
---|---|---|---|
EN 61496-1 | Muting Appendix | Protecting the zone of operation (muting is not active): If the safety-related function block does not detect an active muting operation at its inputs, a SAFEFALSE signal at the S_AOPD_In input (light grid) results in the defined safe state (SAFEFALSE) of the S_AOPD_Out enable output. Activating the muting operation: For a material flow direction from left to right: The muting operation is active if inputs S_MutingSwitch11 and S_MutingSwitch12 both switch from SAFEFALSE to SAFETRUE within the time interval specified at DiscTime11_12. For a material flow direction from right to left: The muting operation is active if inputs S_MutingSwitch21 and S_MutingSwitch22 both switch from SAFEFALSE to SAFETRUE within the time interval specified at DiscTime21_22. Active muting operation: When the muting operation is active, a SAFEFALSE signal at input S_AOPD_In does not result in the defined safe state (SAFEFALSE) of the S_AOPD_Out output.The activated muting operation must be completed within the time specified at MaxMutingTime. If it is not completed within this time, the S_AOPD_Out output is switched to the defined safe state (SAFEFALSE). Completing the muting operation: For a material flow direction from left to right: Muting is deactivated if the S_MutingSwitch21 input and/or S_MutingSwitch22 input switches from SAFETRUE to SAFEFALSE. A SAFEFALSE signal at input S_AOPD_In then switches the S_AOPD_Out output to SAFEFALSE. For a material flow direction from right to left: Muting is deactivated if the S_MutingSwitch11 input and/or S_MutingSwitch12 input switches from SAFETRUE to SAFEFALSE. A SAFEFALSE signal at input S_AOPD_In then switches the S_AOPD_Out output to SAFEFALSE. Invalid muting sequences: States at inputs S_MutingSwitch11, S_MutingSwitch12, S_MutingSwitch21 and S_MutingSwitch22 which are invalid for the muting operation will cause the S_AOPD_Out output to be switched to the defined safe state (SAFEFALSE). Please read the section "Muting error" for more information. Start-up inhibits: Once the function block has been activated, it can execute a start-up inhibit as an option (depending on the setting at S_StartReset). After the function block has detected an invalid muting sequence or another error, that error must be removed and then confirmed by means of a manual reset. This procedure prevents an automatic restart from occurring following error removal. Status of the muting operation: The status of the muting operation is output at the S_MutingActive output of the function block. |
|
EN IEC 62046:2008 | Override depending on muting | Access to the zone of operation in the event of muting errors: A manually operating and muting-dependent override function can be required to clear the zone of operation from objects which cause blockings. However, this function may only be used when the danger potential is calculable, see ISO 12100-2, 4.11.9. Activation: Override may only be activated when at least one muting sensor is active and/or the safety-related equipment is deactivated (input S_AOPD_In = SAFEFALSE). It must not be possible to activate override in the event of faults (other dangerous error states). In addition, it may only enable actions to clear blockings and drive the object outside the zone of operation. Execution: The activation must be initiated by a control device with return spring, a key switch or similar. The trigger must be activated (pressed) for the duration of the override operation and automatically return into its starting position when released. It must be placed in a position with an unlimited view of the zone of operation during the activation and next to an emergency-stop button. Automatic exit: Override must be exited automatically,
|
|
EN ISO 13849-1 | Manual reset device | The Reset input supports the function of a manual reset device.
|
|
EN ISO 12100-2 | Start-up after failure of supply voltage/spontaneous restart | You can select whether the function block will support automatic start-up of the function block or a start-up inhibit
|
|
EN ISO 13849-1 | Category B to 4 | Single-channel or two-channel connection must be implemented depending on the category.
|
|
EN 60204 | Stop functions | The function block (S_AOPD_Out enable signal) executes stop category 0. |