S_EDM_Out output
Output signal for controlling the connected contactors. If all the conditions have been satisfied, the S_EDM_Out output reflects the signal state at the S_OutControl input.
Data type: SAFEBOOL
Hinweis
As the enable signal is present at the S_EDM_Out output, this output is also referred to as the enable output. |
Connection: Connect this output to the coils of the contactors to be monitored.
The enable signal may only control the process directly if this does not adversely affect the safety-related function.
Unintended machine operation
- Verify that the enable signal only controls the process directly if this does not adversely affect the safety-related function.
- Validate the overall safety-related function, including the start-up behavior of the process, and thoroughly test the application.
|
Value | Description |
SAFETRUE | The following conditions must be met:
- The function block has been activated (input Activate = TRUE)
-
and the control signal at the S_OutControl input is SAFETRUE
-
and the connected contactors are functioning correctly (initial state and switching behavior OK)
-
and no start-up inhibit is active (the start-up inhibit is active by default after activating the FB)
-
and the function block has not detected an error.
|
SAFEFALSE | This may be due to one of the following reasons:
- The function block is not activated (input Activate = FALSE)
-
or the control signal at the S_OutControl input is SAFEFALSE
-
or one of the connected contactors is not functioning correctly (initial state or switching behavior not OK)
-
or a start-up inhibit is active (the start-up inhibit is active by default after activating the FB)
-
or the function block has detected an error.
|