S_AOPD_Out output
Output for enable signal of the function block.
The enable signal depends on the status of the protective device and the start-up inhibit.
Data type: SAFEBOOL
This signal represents the state of the safety-related equipment and is the enable signal for the entire process. Connect this signal in the safety logic such that, when the function block outputs a SAFEFALSE signal, the application switches to the defined safe state and retains it.
Hinweis
As the enable signal is present at the S_AOPD_Out output, this output is also referred to as the enable output. |
Connection: Connect the S_AOPD_Out output to an output terminal of your application, either directly or via other safety-related functions/function blocks.
The enable signal may only control the process directly if this does not adversely affect the safety-related function.
Unintended machine operation
- Verify that the enable signal only controls the process directly if this does not adversely affect the safety-related function.
- Validate the overall safety-related function, including the start-up behavior of the process, and thoroughly test the application.
|
Value | Description |
SAFETRUE | No stop function is requested. The following conditions must be met:
- The function block has been activated (input Activate = TRUE)
-
and the light beam of the safety-related equipment (e.g., light barrier) is not interrupted (S_AOPD_In = SAFETRUE)
-
and no start-up inhibit is active (setting made with S_StartReset)
-
and the function block has not detected an error.
Hinweis
When muting is active (S_MutingActive = SAFETRUE) or when an override operation is active (OverrideActive = TRUE), the light beam of the safety-related equipment may be interrupted in accordance with the above conditions. The S_AOPD_Out output remains SAFETRUE. |
|
SAFEFALSE | The stop function is requested. This may be due to one of the following reasons:
- The function block is not active (input Activate = FALSE)
-
or a start-up inhibit is active (setting made with S_StartReset)
-
or the function block has detected an error.
- Monitoring time set at DiscTime11_12 or DiscTime21_22 or MaxMutingTime has elapsed
- or the muting sequence is invalid
- or the light beam of the safety-related equipment (e.g., light barrier) has been interrupted while muting was not active (S_AOPD_In = SAFEFALSE) and no override operation is active (OverrideActive = FALSE)
-
or the override operation is interrupted by the operator (S_StartStopOverride = SAFEFALSE) and the function block detects an error
-
or the override operation has been automatically exited and the function block detects an error.
|
The risk of unintended start-up/restart and/or manipulation can be reduced by combining a stop request from the safety-related application and an operation stop from the standard application.
Unintended start-up
- Make certain that appropriate procedures and measures (according to applicable sector standards) have been established to help avoid hazardous situations when starting up the Sicherheitssteuerung.
- Make certain that no unintended start-up/restart or manipulation can occur.
- Validate the overall safety-related function, including the start-up/restart behavior of the process, and thoroughly test the application.
|
Precise details of the behavior of the S_AOPD_Out output in relation to the start-up inhibit are given in the following table:
Formal parameter | Value | Action | Start-up inhibit | Reset | Enable output |
S_StartReset | SAFETRUE | After function block activation/Sicherheitssteuerung start-up, the start-up inhibit is ... | not active | No action is required at Reset, ... |
- to switch the enable output S_AOPD_Out to SAFETRUE if there is a valid input signal combination.
- to exit the start-up inhibit.
|
SAFEFALSE | active | Reset must be switched from FALSE to TRUE, ... |