S_StartReset input
This input is used to specify the start-up inhibit after the Sicherheitssteuerung has been started up or after the function block has been activated.
When a start-up inhibit is active, all safety-related outputs of the function block are in the defined safe state. This ensures that a machine/system cannot be started up inadvertently. If a start-up inhibit is active, a reset signal is required to remove the inhibit and enable the machine/system to function.
Data
type: SAFEBOOL
Initial value: SAFEFALSE
Connection: Connect this input to a variable or constant.
If Activate = TRUE, the possible values at S_StartReset lead to the following function block behavior:
Value | Description |
---|---|
SAFETRUE | No start-up inhibit for the function block after the Sicherheitssteuerung has been started up and after the function block has been activated. If no start-up inhibit has been specified for the function block, the SAFETRUE status at the S_PSE_In input can cause the S_PSE_Out output to immediately switch to SAFETRUE.Refer to the first warning below this table. |
SAFEFALSE | Active start-up inhibit after the Sicherheitssteuerung has been started up and after the function block has been activated.The active start-up inhibit must be manually removed by means of a reset signal at the Reset input.Removing the start-up inhibit by means of a positive signal edge at the Reset input can cause the S_PSE_Out output to switch to SAFETRUE immediately (depending on the status of the other inputs).Refer to the second warning below the table. |
WARNUNG
|
Unintended start-up If no start-up inhibit is specified:
|
WARNUNG
|
Unintended start-up
|
The start-up inhibit must only be deactivated (S_StartReset = SAFETRUE) if it is certain that starting up the machine/system will not lead to a hazardous situation or that a suitable start-up inhibit is in place at another location or using other means.
WARNUNG
|
Non-conformance to safety function requirements
|
WARNUNG
|
Non-conformance to safety function requirements Verify that a start-up inhibit facility is implemented in your safety-related network if required for your specific safety-related function according to the relevant standards. |
WARNUNG
|
Unintended start-up Validate the behavior of the function block and the safety-related network as a whole and thoroughly test the application. |