Implementation of safety requirements from applicable standards
The safety-related function block has been developed according to the safety requirements (from applicable standards) listed in this section. All other requirements from these standards must be observed when implementing the safety-related function.
This section describes either how the function block meets the requirements of the standards or what measures need to be taken to meet the requirements of the standards.
Standards | Context/Requirement | Implementation | |
---|---|---|---|
ISO 13856-1: 2013 | Pressure-sensitive protective devices | Part 1: General principles for the design and testing of pressure-sensitive mats and pressure sensitive
floors. Chapter 4.7: Response of output signal switching device(s) to the actuating force. |
|
ISO 13856-2: 2013 | Pressure-sensitive protective devices | Part 2: General principles for the design and testing of pressure-sensitive edges and
pressure-sensitive bars. Chapter 4.11: Reset function. |
|
ISO 13856-3: 2013 | Pressure-sensitive protective devices | Part 3: General principles for design and testing of pressure-sensitive bumpers, plates, wires and similar devices. Chapter 4.2.6.3: Reset function. Chapter C.2.8: Result of sensor actuation. |
|
EN ISO 12100-2 | Start-up after failure of supply voltage/spontaneous restart | The function block supports a start-up inhibit and/or restart inhibit of the function block after
|
|
EN ISO 13849-1 | Manual reset device | The Reset input supports the function of a manual reset device.
|
|
EN ISO 13849-1 | Category B to 4 | Single-channel or two-channel connection must be established depending on the category.
|
|
EN 60204 | Stop functions | The function block (S_PSE_Out enable signal) executes stop category 0. | |
ISO 13856 | Start-up inhibit function | The function block supports a start-up inhibit and/or restart inhibit of the function block after
|