Profinet Warning (PNIO0112): The device "..." cannot be updated cyclically faster than "...".
This warning is reported when the update time of the cyclic exchange of IO data between Profinet controller and Profinet device is lower than the minimum value given in the warning. The update time is a product of the controller's send clock, the Profinet timebase and the reduction ratio. If the update time is lower than the minimum value, the Profinet device may reject the connection request.
Double-clicking the warning jumps to the device parameter ('Update time' for inputs or outputs; read-only value) that causes the warning. To resolve the error, select a reduction ratio from the 'Reduction ratio (symmetric/inputs)' list box that produces an update time that is higher than the minimum time given in the message.