Done output
Output for signaling "function block processing completed".
Data type: SAFEBOOL
Connection: If required, the signal can be connected to a variable of the SAFEBOOL data type or to other safety-related functions/function blocks.
| Value | Description | 
| SAFETRUE | 
The DiagCode = 8000 is shown.
Function block is activated (Activate = TRUE) and
the function block has deleted the specified data set in the recipe file. i.e., has overwritten its content with 0-values. 
 
| Note 
 
The delete operation may last several Safety PLC cycles. Therefore, Done may only be set to SAFETRUE after a few cycles after switching the CommandDelete input to SAFETRUE.After a successful delete operation, output Done remains SAFETRUE until the next operation, even if the CommandDelete input is switched back to SAFEFALSE. With a new SAFETRUE signal at CommandDelete, Done is always switched to SAFEFALSE. |  | 
| SAFEFALSE | 
Refer to...
Function block is either not activated (Activate = FALSE, DiagCode = 0000), or
an error occurred due to an invalid value applying at a function block input (e.g., IDRecipeFile out of valid range), or
the addressed recipe file is not accessible/not existent, or
the function block processing is still in progress, or
an error occurred during the processing, for example, because the file to be modified is in use or the flash memory of the standard controller could not be accessed. 
... the help topic "Fault avoidance" where the handling of various potential error scenarios is explained.... the diagnostic code value present at the DiagCode output for details. |