OverridePossible output
Output for the monitoring signal providing notification that an override operation is possible:
Data type: BOOL
Connection: Connect the OverridePossible output to an output terminal of your application (e.g., for an indicating device to signal that an override operation is possible), either directly or via other functions/function blocks.
| Value | Description | 
| TRUE | Override operation is possible. The following conditions must be met: 
The function block has been activated (input Activate = TRUE) 
and a muting error is present
and the light beam of the safety-related equipment (e.g., light barrier) is interrupted (S_AOPD_In = SAFEFALSE) 
or at least one of the muting sensors detects an object. | 
| FALSE | Override operation is not  possible.The following conditions must be met: 
The function block is not active (input Activate = FALSE)
or no muting error is present
or the light beam of the safety-related equipment (e.g., light barrier) is not interrupted (S_AOPD_In = SAFETRUE) 
or none of the muting sensors detects an object. | 
| Non-conformance to safety function requirements 
 
Be sure that your risk analysis includes an evaluation of a manual override operation (S_StartStopOverride = SAFETRUE).Observe the regulations given by relevant sector standards regarding the override operation.Make certain that appropriate procedures and measures (according to applicable sector standards) have been established to help avoid hazardous situations when activating the override operation. |