S_MutingActive output
Output for the status of the muting operation.
Data type: SAFEBOOL
Connection: Connect the S_MutingActive output to an output terminal of your application (for a muting lamp, for example), either directly or via other safety-related functions/function blocks.
The signal (S_MutingActive) may only control the process directly if this does not adversely affect the safety-related function.
| Unintended machine operation 
 
Verify that the S_MutingActive signal only controls the process directly if this does not adversely affect the safety-related function.Validate the overall safety-related function, including the start-up behavior of the process, and thoroughly test the application. | 
| Value | Description | 
| SAFETRUE | This indicates that muting is active. The following conditions must be met. 
 
| Note If muting is active (S_MutingActive = SAFETRUE), the light beam of the safety-related equipment may be interrupted. The S_AOPD_Out output remains SAFETRUE.
 |  | 
| SAFEFALSE | Muting is not active. This may be due to one of the following reasons: 
Muting has not been activated by the muting sensors
or the function block is not activated (input Activate = FALSE)
or the function block has detected an error.
The muting sequence is invalidor the monitoring time set at MaxMutingTime has elapsed. 
 
| Note If muting is not active, an interruption of the light beam of the safety-related equipment will cause the S_AOPD_Out output to be switched to the defined safe state (SAFEFALSE).
 |  |