Diagnostic codes
Note
This documentation refers to the monitored electro-sensitive protective equipment as ESPE for short. |
The hexadecimal diagnostic codes listed here are output as WORD data type at the DiagCode output of the function block.
Code (hex) | Description | Options for remedy |
---|---|---|
0000 | The function block is not activated. The Activate input is FALSE. Depending on the connection of Activate, the inactive function block can also indicate an error in the connected periphery. | Activate the function block by switching Activate to TRUE.Correct the error in the periphery according to the device description. |
8000 | The ESPE has not triggered (S_ESPE_In = SAFETRUE). | No measures required. |
8001 | The function block is activated. This state of the function block is completed after one cycle of the Safety PLC. | No measures required. |
8002 | The start-up inhibit is specified with S_StartReset = SAFEFALSE.
|
|
8003 | The ESPE is no longer triggered (S_ESPE_In = SAFETRUE). The start-up inhibit of the function block is active. | Perform a reset on the function block. |
8004 | ESPE has triggered (S_ESPE_In = SAFEFALSE).
|
|
8005 | The ESPE is no longer triggered. The restart inhibit of the function block is active (S_AutoReset = SAFEFALSE). | Perform a reset on the function block. |
C001 | Once the request for the safety-related function of the ESPE has been removed, a permanent TRUE is detected at Reset. |
|
C002 | Once the request for the safety-related function of the ESPE has been removed, a permanent TRUE is detected at Reset. |
|