MaxOverrideTime input
Specification of the maximum permissible time (in seconds) for the entire override operation. If the override operation is not completed within this time, the S_AOPD_Out output is switched to the defined safe state SAFEFALSE and the function block signals an error (Error is set to TRUE).
Data type: TIME
Initial value: #60s
Connection: Connect this input to a time literal, i.e., to a constant of the data type TIME.
This timer starts when the override operation is initiated by the operator (S_StartStopOverride input switches to SAFETRUE).
If the override operation is interrupted (S_StartStopOverride switches to SAFEFALSE), the override timer continues to run. If the override operation is not restarted within the set time (S_StartStopOverride switches to SAFETRUE), the function block signals an error (Error = TRUE).
WARNUNG
|
Non-conformance to safety function requirements
|
Minimum value: 0 s
Maximum value: 600 s