SF_MutingPar_2Sensor

Help version 2.0 / Issue date: 2024.04
The following description is valid for the function block SF_MutingPar_2Sensor, Version 2.0z (where z = 0 to 9).

Short Description The safety-related SF_MutingPar_2Sensor function block evaluates the signals of two muting sensors and an optoelectronic safety-related equipment (a light grid, for example) in an application for parallel muting with two sensors and switches the enable signal at the S_AOPD_Out output.

The signal at the S_AOPD_Out output is the enable signal for the entire process. A SAFEFALSE signal at the S_AOPD_Out output stops the application in the zone of operation.

This function can be used to temporarily deactivate (or "mute") safety-related equipment in the form of a light grid, for example, in order to allow an object which has been identified by the muting sensors as permissible (for the muting operation) to pass through on an assembly conveyor.
In such a case, the interruption of the light grid does not have any effect on the S_AOPD_Out output.

By contrast, if the safety-related equipment is engaged by an object which has not been identified by the muting sensors as permissible, the S_AOPD_Out output switches to SAFEFALSE.
For example, if the hand of a worker passes through an assembly conveyer interrupting a light curtain, the S_AOPD_Out output would be used to signal the actions necessary to set the zone of operation to its defined safe state.

In the event of a muting error, the safety-related shutdown requested by the safety function can be temporarily deactivated by means of the integrated override function, e.g., in order to move an impermissible object which caused the muting error outside the zone of operation. The override function must be manually requested by the operating personnel as long as the object is in a safeguarded area or the override function has been automatically exited.

A start-up inhibit can be specified at S_StartReset.
Illustration of ApplicationThe graphic below illustrates an application for the SF_MutingPar_2Sensor function block.

Weitere Infos
The entire muting operation is divided into different muting sequences. For more detailed information (including override), see the functional description.

MS_11: Muting sensor, connected to the S_MutingSwitch11 function block input
MS_12: Muting sensor, connected to the S_MutingSwitch12 function block input

S, R: Transmitter and receiver of the light grid

KS: Control device (e.g., key switch) for override

!: Zone of operation
Block Icon
Inputs Activate

S_AOPD_In

S_MutingSwitch11 and S_MutingSwitch12

DiscTimeEntry

MaxMutingTime

MaxOverrideTime

MutingEnable

S_StartStopOverride

S_StartReset

Reset
Outputs Ready

S_AOPD_Out

S_MutingActive

OverridePossible

OverrideActive

SafetyDemand

ResetRequest

Error

DiagCode
Detailed informationSignal sequence diagram

Application example

Function block instantiation

 

Additional information is available in the following sections: