-

EDM1 and EDM2 inputs

State-controlled signal inputs for feedback signals from contactors. These inputs are connected to the N/C contacts of the contactors. Various connection options are illustrated in the application examples.

Data type: BOOL
Initial value: FALSE

If only one feedback signal is used, this must be connected in parallel to both inputs.

Connection: Connect these inputs directly to the feedback signals (N/C contacts) of the contactors to be monitored or via additional safety-related functions/function blocks. Constant TRUE or FALSE values are not permitted.

If the function block is activated (input Activate = TRUE), the possible values at this input lead to the following function block behavior:

ValueDescription
TRUEA feedback signal is present. The connected contactor has dropped out (initial state).
FALSENo feedback signal is present. The connected contactor is picked up (switching state).

Verifying the initial state

If the connected contactors are in the initial state, the feedback signal at inputs EDM1 and EDM2 must be TRUE.

The initial state is verified by the function block if:

Verifying the switching behavior

Once the S_EDM_Out output switches to SAFETRUE, the feedback signal at the EDM1 and EDM2 inputs must become FALSE within the permissible response time specified at MonitoringTime. Otherwise, the function block outputs an error message (output Error = TRUE) and the S_EDM_Out output switches to the defined safe state (SAFEFALSE).
If the S_EDM_Out output switches from SAFETRUE to SAFEFALSE, the switching operation is also monitored. The feedback signal at the EDM1 and EDM2 inputs must become TRUE within the permissible response time set at MonitoringTime.