MonitoringTime input
Specification of the maximum permissible response time of the connected contactors.
Data type: TIME
Initial value:
#0ms
Connection: Connect this input to a time literal, i.e., to a constant of the data type TIME.
Once the S_EDM_Out output switches to SAFETRUE, the feedback signal at the EDM1 and EDM2 inputs must become FALSE within the response time specified here. Otherwise, the function block outputs an error message (output Error = TRUE) and the S_EDM_Out output switches to the defined safe state (SAFEFALSE).
The process of switching off the connected contactors is also time-monitored: if the S_EDM_Out output switches from SAFETRUE to SAFEFALSE, the switching operation of the contactors is also monitored. The feedback signal at the EDM1 and EDM2 inputs must become TRUE within the permissible response time set at MonitoringTime.
WARNUNG
|
Non-conformance to safety function requirements
|