DiscTime21_22 input
Specification of the permissible discrepancy time for the switching operation of the muting sensors at the S_MutingSwitch21 and S_MutingSwitch22 inputs.
Data type: TIME
Initial value: #0ms
Connection: Connect this input to a time literal, i.e., to a constant of the data type TIME.
Once the first input has switched to TRUE, the second input must follow within the time set at DiscTime21_22. If both inputs switch to TRUE within this time, active muting remains active (S_MutingActive = SAFETRUE).
Hinweis
If muting is active (S_MutingActive = SAFETRUE), the light beam of the safety-related equipment may be interrupted. The S_AOPD_Out output remains SAFETRUE. |
The time set at DiscTime21_22 is exceeded if the second muting sensor input does not switch to TRUE within the set duration. The S_AOPD_Out enable output is then switched to the defined safe state SAFEFALSE and the function block signals an error (Error = TRUE).
Weitere Infos
Also refer to the example muting operation procedure shown in the functional description for this function block. |
WARNUNG
|
Non-conformance to safety function requirements
|
Minimum value: 0 s
Maximum value: 4 s