MaxMutingTime input
Specification of the maximum permissible time for the entire muting operation. If the muting operation is not completed within this time, the S_AOPD_Out output is switched to the defined safe state SAFEFALSE and the function block signals an error (Error switches to TRUE).
Data type: TIME
Initial value: #0ms
Connection: Connect this input to a time literal, i.e., to a constant of the data type TIME.
The following is valid for a material flow direction from left to right:
- This timer starts when at least one muting sensor of the first parallel sensor pair (in this case, input S_MutingSwitch11 or S_MutingSwitch12, sensor located before the safety-related equipment) provides a SAFETRUE signal (i.e., there is an object inside the detection area of the sensor).
- The muting operation is complete when at least one muting sensor of the second parallel sensor pair (S_MutingSwitch21 or S_MutingSwitch22, sensor located behind the safety-related equipment) provides SAFEFALSE again.
The following is valid for a material flow direction from right to left:
- This timer starts when at least one muting sensor of the first parallel sensor pair (in this case, input S_MutingSwitch21 or S_MutingSwitch22, sensor located before the safety-related equipment) provides a SAFETRUE signal (i.e., there is an object inside the detection area of the sensor).
- The muting operation is complete when at least one muting sensor of the second parallel sensor pair (S_MutingSwitch11 or S_MutingSwitch12, sensor located behind the safety-related equipment) provides SAFEFALSE again.
Weitere Infos
Also refer to the example muting operation procedure shown in the functional description for this function block. |
WARNUNG
|
Non-conformance to safety function requirements
|
Minimum value: 0 s
Maximum value: 120 m