MaxMutingTime input

Specification of the maximum permissible time for the entire muting operation. If the muting operation is not completed within this time, the S_AOPD_Out output is switched to the defined safe state SAFEFALSE and the function block signals an error (Error switches to TRUE).

Data type: TIME
Initial value: #0ms

Connection: Connect this input to a time literal, i.e., to a constant of the data type TIME.

The following is valid for a material flow direction from left to right:

The following is valid for a material flow direction from right to left:

Weitere Infos
Also refer to the example muting operation procedure shown in the functional description for this function block.

WARNUNG
Non-conformance to safety function requirements
  • Verify that the time value set at MaxMutingTime corresponds to your risk analysis.
  • Be sure that your risk analysis includes an evaluation for incorrectly setting the time value for the MaxMutingTime parameter.
  • Validate the overall safety-related function with regard to the set MaxMutingTime value and thoroughly test the application.

Minimum value: 0 s
Maximum value: 120 m