TestExecuted output

Output for signaling the status of the sensor test.

Data type: BOOL

A TRUE signal at the TestExecuted output results that the sensor test has been completed without errors.

Hinweis
The enable signal at the S_OSSD_Out output can be SAFETRUE even if there is no TRUE signal at TestExecuted.
The automatic test has to be performed with positive results for the safety-related sensor to function correctly.

Connection: Connect the TestExecuted output to a global I/O variable or via additional functions/function blocks in order to transmit the signal externally for diagnostic purposes (e.g., controlling a signal lamp).

ValueDescription
TRUE The automatic sensor test has been performed successfully.

Hinweis
After a successful test, TestExecuted retains the TRUE status until a new sensor test is requested at the StartTest input.

FALSEThe automatic sensor test
  • has not yet been performed.
  • or is currently in progress
  • or has been carried out with errors.
Refer to the warning below this table.

WARNUNG
Non-conformance to safety function requirements
  • Regularly check the safety-related sensor by periodically switching the StartTest input from FALSE to TRUE in accordance with the risk analysis.
  • Make certain that appropriate procedures and measures have been established to help avoid hazardous situations when applying TRUE to the StartTest input.