'Submodule List' Editor (Profinet Module)

The following information refers to a specific, typical device type. Your screen may differ.

This help topic describes the 'Submodule List' editor of a Profinet module PLANT node. Profinet modules are child elements of a Profinet device under the 'Profinet' node. This tabular editor contains the Profinet submodules of the Profinet (I/O) module. The content of the table is read from the device description of the I/O module.

Profinet submodules have a purely structuring function. The actual inputs and outputs (channels) of a Profinet I/O module are implemented in its submodules. As acyclic services always address the submodules, a module must always have at least one submodule.

ColumnDescription
#Number of the Profinet submodule. The number of lines (available submodules) in the table depends on the Profinet module.
TypeType of the Profinet submodule.
FunctionFunction description appropriate to the Profinet specification. The parameter is still available after a firmware update.

The 'Function' text is shown in the device node name (preceding the type) in the PLANT.

Max. string length: 32 characters
LocationInstallation location appropriate to the Profinet specification. The parameter is still available after a firmware update.

If no 'Function' is specified, the 'Location' text is visible in the tree.

Max. string length: 32 characters
ActiveDrop-down list for activating/deactivating the submodule. Select 'Yes' to enable the submodule function.
NodeIDIndicates the position of the submodule.
This number corresponds to the number (#) of the higher-level I/O module in the Module List of the Profinet device.

Further Info
Refer to the topic "Inserting Devices/Modules in the Station Editor" for more details and procedures how to work with the station editor.